1. General
VS1 series vacuum circuit breaker is indoor high voltage switch-gear with rated voltage 7.2-12kV, three-phase AC 50Hz, It is used for the This product conforms to the national standard GB1984-2003 "Alternate current high-voltage circuit breaker", and international standard IEC 62271-100"High-voltage alternate current circuit breaker".
The Circuit breaker can be used to protect and control electrical equipment in the industrial & mineral enterprise, power plant and substation as well as to switch infrequent operating places. It has high credibility of operation and longevity of service.
The form of circuit breaker assembled in switchgear could be draw out type as well as fixed installation type.
2. Service Environment
Altitude:1000m and below;
Environmental temperature is from:-15~40°C;
Environmental humidity:
Daily average of relative humidity≤95%
Daily average saturated vapor pressure≤2.2×10-3Mpa
Monthly average of relative humidity≤90%
Monthly average saturated vapor pressure≤1.8×10-3Mp
No operating in such environment as subject to dust, dirt, smog, corrosive/flammable gas, vapor and salt pollution.
Earthquake intensity: No more than 8 degree.
The circuit breaker should be operated in the normal service condition. If there is any difference between actual service condition and normal service condition, for example, the altitude of installed place is above 1000m, the value of ambient air temperature exceed specified limit or the place with high humidity where easy to course moist, it should be conformed by the manufacturer.
3. Technical data
|
Code |
Item |
Unit |
Data |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
rated frequency |
Hz |
50 |
|
3 |
Rated lighting impact withstand voltage(peak value) |
kV |
75 |
|
4 |
power frequency withstand voltage (1 min) |
kV |
42 |
|
5 |
Rated current |
A |
630 630 1250 1250 1250 1600 |
|
6 |
Rated short-circuit breaking current |
kV |
20 25 31.5 |
|
7 |
Rated short-time withstand current (virtual value) |
kV |
20 25 31.5 |
|
8 |
Rated peak withstand current (peak value) |
kV |
50 63 80 |
|
9 |
Rated short-circuit making current (peak value) |
kV |
50 63 80 |
|
10 |
Duration of rated short-circuit current |
s |
4 |
|
11 |
Rated operating order |
? |
0-0.3-CO-180S-CO 0-180S-CO-180S-CO |
|
12 |
Rated breaking current of single/symmetrical capacitor bank |
A |
630/400 (40kA:800/400) |
|
13 |
Rated making surge current of capacitor bank |
kV |
20 (frequency:4250Hz) |
|
14 |
Contact clearance |
mm |
11±1 |
|
15 |
Contact travel |
mm |
3.5±0.5 |
|
16 |
Bounce time of contact making |
ms |
≤2 |
|
17 |
Out of simultaneity of three-phase making and breaking |
ms |
≤2 |
|
18 |
Average breaking speed |
m/s |
0.9~1.2 |
|
19 |
Average making speed |
m/s |
0.5~0.8 |
|
20 |
Breaking time (rated voltage) |
ms |
20~50 |
|
21 |
Making time (rated voltage) |
ms |
35~70 |
|
22 |
Rated operation voltage of making and breaking |
V |
AC110/220, DC110/220 |
|
23 |
Rated voltage of energy storage motor |
V |
AC110/220, DC110/220 |
|
24 |
Rated power of energy storage motor |
W |
70,100 (40kA) |
|
25 |
Energy storage time |
s |
≤15 |
|
26 |
Permitted abrasion thickness of dynamic and static contacts |
mm |
≤3 |
|
27 |
Rebound amplitude of contact breaking |
mm |
≤2 |
|
28 |
Main circuit resistance |
? |
630A ≤50µΩ 1250A ≤45µΩ |